Industrial processing of plastics
ČeskyEnglishPусский

CHVV-800

These are  induced draft cooling towers for large operations . Supporting construction is hot-dip galvanized steel with fiberglass casing and with axial fan on the top of the cooling tower.   Large induced draft cooling towers are installed onto reinforced concrete accumulating basin serving as foundation for cooling tower. Basic arrangement of cooling tower sections is "in line", where the number of sections is given by quantity of cooling water.

Key features:

  • mounted onto reinforced concrete accumulating basin
  • hot-dip galvanized steel or composite (FRP) construction with fiberglass casing
  • water distribution by PVC pipes and spraying nozzles
  • cooling fill and eliminators from PP or PVC
  • fan unit with low speed motor and composite (FRP) blades

Technical data of CHVV-800
Operation parameters
Water flow range m3/h 400 - 1200
Nominal water flow m3/h 800
Maximal inlet water temp. °C 65
Drift losses % 0,007
Evaporation (Dt = 10°C and air temp. 28 - 30 °C) % 1,5
Pressure in inlet pipe m w.c. 3 ÷ 15
Cooler construction
Type of cooling tower   counter flow, induced draft
Cell dimensions m 8 x 8 x 6,90
Number of flanges mm DN400
Watered surface m2 64
Fan unit
Fan type   axial
Motor-gearbox-fan coupling   direct
Fan diameter mm 5000 ÷ 4500
Motor rated power kW 37 ÷ 40
Electric motor V/Φ/f 400/3/50
Protection/isolation class   IP55 F
 