These are  induced draft cooling towers for large operations . Supporting construction is hot-dip galvanized steel with fiberglass casing and with axial fan on the top of the cooling tower.   Large induced draft cooling towers are installed onto reinforced concrete accumulating basin serving as foundation for cooling tower. Basic arrangement of cooling tower sections is "in line", where the number of sections is given by quantity of cooling water.

Key features:

  • mounted onto reinforced concrete accumulating basin
  • hot-dip galvanized steel or composite (FRP) construction with fiberglass casing
  • water distribution by PVC pipes and spraying nozzles
  • cooling fill and eliminators from PP or PVC
  • fan unit with low speed motor and composite (FRP) blades

Technical data of CHVV-600
Operation parameters
Water flow range m3/h 500 - 1000
Nominal water flow m3/h  
Maximal inlet water temp. °C 65
Drift losses % 0,007
Evaporation (Dt = 10°C and air temp. 28 - 30 °C) % 1,5
Pressure in inlet pipe m w.c. 3 ÷ 5
Cooler construction
Type of cooling tower   counter flow, induced draft
Number of cells pcs any
Cooler dimensions m 8,10 x 8,00
Cell dimensions m 8,10 x 8,00
Height of inlet pipe with/without basin m 3,58
Total height with/without basin m 6,90
Number of flanges mm 2 x DN300
Watered surface m2 64
Fan unit
Number of fans pcs 1 (2)
Fan type   axial
Motor-gearbox-fan coupling   direct
Fan diameter mm 4500
Fan speed rpm 485
Motor rated power kW 37 (55)
Electric motor V/Φ/f 400/3/50
Protection/isolation class   IP55 F
Note: in (brackets) data for two-section arrangement of cooling tower