Industrial processing of plastics
ČeskyEnglishPусский

CHVV-2200

These are  induced draft cooling towers for large operations . Supporting construction is hot-dip galvanized steel with fiberglass casing and with axial fan on the top of the cooling tower.   Large induced draft cooling towers are installed onto reinforced concrete accumulating basin serving as foundation for cooling tower. Basic arrangement of cooling tower sections is "in line", where the number of sections is given by quantity of cooling water.

Key features:

  • mounted onto reinforced concrete accumulating basin
  • hot-dip galvanized steel or composite (FRP) construction with fiberglass casing
  • water distribution by PVC pipes and spraying nozzles
  • cooling fill and eliminators from PP or PVC
  • fan unit with low speed motor and composite (FRP) blades

Technical data of CHVV-2200
Operation parameters
Water flow range m3/h 1200 - 3500
Nominal water flow m3/h 2200
Maximal inlet water temp. °C 65
Drift losses % 0,007
Evaporation (Dt = 10°C and air temp. 28 - 30 °C) % 1,5
Pressure in inlet pipe m w.c. 3 ÷ 15
Cooler construction
Type of cooling tower   counter flow, induced draft
Cell dimensions m 16 x 12 x 10,40
Number of flanges mm 4 x DN300
Watered surface m2 192
Fan unit
Fan type   axial
Motor-gearbox-fan coupling   direct
Fan diameter mm 7000
Motor rated power kW 75
Electric motor V/Φ/f 400/3/50
Protection/isolation class   IP55 F
 

These buttons will support and recommend our site to other Internet users. Thank you.

MYTECH s.r.o

Skaštice 159
76701 Kroměříž

Phone: +420 573 504 142
Email:

Partners MYPLAST - production and processing of plastic Web Design Studio Taox is also the author of Web sites